Eaton Logo, links to the Eaton homepage

Eaton 5125 UPS Technical Specs

Battery Runtimes 
Part Number 51250500A 51251500A 51252000A 51252200A
Rating 1000VA 1500VA 2000VA 2200VA
Capacity (VA/Watts) 1000/700 1500/1050 2000/1400 2200/1600
Dimensions WxDxH (mm) 162 x 401 x 250 162 x 467 x 249 205 x 493 x 250 205 x 493 x 250
Weight (kg) 16 23 31 31
Typical runtime
(Full load)
5 min 6 min 6 min 5 min
Input Connection IEC320/10A IEC320/10A IEC320/10A IEC320/16A
Output Connection 4 x Aust. 10A 6 x Aust. 10A
Operational
Nominal input voltage (Vac) 220/230/240 Vac
Input Voltage Range 166-276 VAC (+15/-30% of nominal)
Operating Frequency 50/60 Hz, Auto-sensing
Input power factor Same as load
Nominal output voltage 220/230/240 VAC
Output voltage regulation -10%/+6% of selected nominal voltage
Overload capacity 110% 3 min; 150% 10 cycles
Efficiency 95%
User interface
LED Information LED display
Standard communication ports RS232
Optional SNMP/WEB card, USB card, relay cards
Environmental 
Operating Temperature  0 to +40º C
Storage Temperature -15 to +55º C
Altitude  < 3000m
Audible Noise at 1 metre < 45dB normal mode
< 50dB battery mode
Certification
Markings CE/GS/UL/C-Tick
Safety EN 50091-1-1 & UL 1778
EMC EN 50091-2, EN6100-3-2

Go to top


Eaton 5125 Battery Run Time Chart (in minutes full load/half load)

Model Standard Internal
Batteries
1 EBM 2 EBMs 3 EBMs 4 EBMs
Tower Models
1000VA 5/16 48/110 100/220 170/6h 4h/8h
1500VA 6/17 33/79 63/146 92/174 120/201
2000VA 6/15 30/70 60/190 90/215 120/240
2200VA 5/14 26/60 55/170 81/198 106/224
E-mail this page Print this page
Copyright ©2009 Eaton Corporation.