| Part Number | 51250500A | 51251500A | 51252000A | 51252200A |
| Rating | 1000VA | 1500VA | 2000VA | 2200VA |
| Capacity (VA/Watts) | 1000/700 | 1500/1050 | 2000/1400 | 2200/1600 |
| Dimensions WxDxH (mm) | 162 x 401 x 250 | 162 x 467 x 249 | 205 x 493 x 250 | 205 x 493 x 250 |
| Weight (kg) | 16 | 23 | 31 | 31 |
| Typical runtime (Full load) |
5 min | 6 min | 6 min | 5 min |
| Input Connection | IEC320/10A | IEC320/10A | IEC320/10A | IEC320/16A |
| Output Connection | 4 x Aust. 10A | 6 x Aust. 10A | ||
| Operational | |
| Nominal input voltage (Vac) | 220/230/240 Vac |
| Input Voltage Range | 166-276 VAC (+15/-30% of nominal) |
| Operating Frequency | 50/60 Hz, Auto-sensing |
| Input power factor | Same as load |
| Nominal output voltage | 220/230/240 VAC |
| Output voltage regulation | -10%/+6% of selected nominal voltage |
| Overload capacity | 110% 3 min; 150% 10 cycles |
| Efficiency | 95% |
| User interface | |
| LED Information | LED display |
| Standard communication ports | RS232 |
| Optional | SNMP/WEB card, USB card, relay cards |
| Environmental | |
| Operating Temperature | 0 to +40º C |
| Storage Temperature | -15 to +55º C |
| Altitude | < 3000m |
| Audible Noise at 1 metre |
< 45dB normal mode < 50dB battery mode |
| Certification | |
| Markings | CE/GS/UL/C-Tick |
| Safety | EN 50091-1-1 & UL 1778 |
| EMC | EN 50091-2, EN6100-3-2 |
Eaton 5125 Battery Run Time Chart (in minutes full load/half load)
| Model | Standard
Internal Batteries |
1 EBM | 2 EBMs | 3 EBMs | 4 EBMs |
| Tower Models | |||||
| 1000VA | 5/16 | 48/110 | 100/220 | 170/6h | 4h/8h |
| 1500VA | 6/17 | 33/79 | 63/146 | 92/174 | 120/201 |
| 2000VA | 6/15 | 30/70 | 60/190 | 90/215 | 120/240 |
| 2200VA | 5/14 | 26/60 | 55/170 | 81/198 | 106/224 |